Order Separately . . .
PETK Power and End Termination Kits (per cable)
PETK-1 for RSX, TSX, VSX, BSX
PETK-2 for BSX, KSX, HTSX
PETK-3 for HPT, FP
Item Quantity Description
1 1 RTV Tube (per cable)
2 1 Power Connection Boot
3 2 Conductor Wire Pins (per cable)
4 1 Brad Wire Pin (per cable)
5 1 Ground Sleeve (per cable)
6 1 Power Gland (Optional see Step 10)
1
2 4
3 5
Tools Required . . .
Terminator-LN-Tool
(order separately)
3 mm
8 mm
28 mm
29 mm
33 mm
Kit Contents . . .
Item Quantity Description
1 1
Expediter Assembly
Support Cap with O-Ring
Threaded Grommet Compressor
Grommet
Support Base with O-Ring
2 1 Junction Box Lid
3 1 Junction Box Base with O-Ring
4 1 Nut
5 1 Banding
6 1 Banding Guide
7 1
Terminal Blocks with DIN Rail
(Refer to terminal specifications for maximum
allowable wire size)
8 1 Junction Box Cord
9 2 Blind Plugs
1
2
6
4
3
8
5
7
9
6
Dimensions . . .
Terminator
TM
ZL INSTALLATION PROCEDURES
Certifications/Approvals . . .
1725 II 2 GD Ex eb IIC T4-T6, Ex tb IIIC T135°C-T85°C FM 10ATEX0058X
IP66 -60°C Ta +55°C
Ordinary & Hazardous Locations
IECEx FMG 10.0022X Ex eb IIC T4-T6, Ex tb IIIC T135°C-T85°C
Warnings . . .
• Duetotheriskofelectricalshock,arcingandrecausedby
product damage or improper usage, installation or mainte-
nance, a ground-fault protection device is required.
• InstallationmustcomplywithThermon requirements (in-
cluding form PN 50207U for Ex systems) and be installed
in accordance with the regulations as per the norm EN IEC
60079-14 for hazardous areas (where applicable), or any
other applicable national and local codes.
• Componentapprovalsandperformanceratingsarebased
on the use of Thermon specified parts only.
• De-energizeallpowersourcesbeforeopeningenclosure.
• Keependsofheatingcableandkitcomponentsdrybefore
and during installation.
• Minimumbendingradiusofheatingcableis32mm(except
HPT is 57 mm and FP is 19 mm).